Nader – Leading Low-voltage Eletrical Component Manufacturer

Founded in 1999, Nader (Shanghai Liangxin Electrical Co., LTD.) boasts a team of professionals with vast experience in technological research and development and production management. The head office of the company is located in Shanghai’s Pudong New District. Now the company is one of the fastest growing large private enterprises in domestic low-voltage electrical apparatus industry. As a Nader product supplier of worldwide customers, we positioned ourselves as a customer-friendly enterprise.  We should be oriented by customer requirement. We create value for customers by technical advice, and by providing differentiated products, system solutions and sales services.

 

Low-Voltage Final Distribution Products

NDM1-63 Series MCB

Application

• B Curve: Non-inductive or micro-inductive loads
• C Curve: Usual inductive loads
• D Curve: Highly inductive loads
• Overload and short circuit protection

  Product Name   NDM1-63 Series MCB
  Standards and Certificates   IEC60898-1. With TÜV; CE; CCC certificates.
  Rated Voltage   AC 230V/400V; DC 60V
  Rated Current   1A~63A
  Breaking Capacity   1A~40A 6kA; 50A, 63A 4.5kA
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   B, C & D Curve
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables upto 25 sq. mm
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release
NDB1 Series MCB (1P+N)

Application

• In TT/TN-S grounding system
• Phase and neutral protection against short circuit and overload

  Product Name   NDB1 Series MCB (1P+N)
  Standards and Certificates   IEC60898-1; CCC.
  Rated Voltage   AC 230V
  Rated Current   6A~32A
  Breaking Capacity   4.5kA
  Isolation Function   /
  Number of Poles   1P+N
  Tripping Characteristics   C Curve (5In~10In)
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables up to 10 sq. mm
  Electric Accessories   /
NDB2-63 Series MCB

Application

• B Curve: Non-inductive or micro-inductive loads
• C Curve: Usual inductive loads
• D Curve: Highly inductive loads
• Overload and short circuit protection

  Product Name   NDB2-63 Series MCB
  Standards and Certificates   UL1077, IEC 60898-2; UL1077, TÜV, CE, CCC
  Rated Voltage   AC 230V/400V, AC 277V, DC 60V
  Rated Current   1A~63A
  Breaking Capacity   10kA as per IEC60898; 7.5kA as per UL1077
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   B, C & D Curve
  Mechanical Endurance   20000 times
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release
NDB2-63K Series MCB (1P+N)

Application

• In TT/TN-S grounding system
• Phase and neutral protection against short circuit and overload

  Product Name   NDB2-63K Series MCB (1P+N)
  Standards and Certificates   IEC 60898-1; CCC
  Rated Voltage   AC 230V
  Rated Current   6A~63A
  Breaking Capacity   6kA
  Isolation Function   /
  Number of Poles   1P+N
  Tripping Characteristics   C Curve (5In~10In)
  Mechanical Endurance   20000 times
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   /
NDB2T-63 Series MCB

Application

• B Curve: Non-inductive or micro-inductive loads
• C Curve: Usual inductive loads
• D Curve: Highly inductive loads
• Overload and short circuit protection

  Product Name   NDB2T-63 Series MCB
  Standards and Certificates   IEC 60947-2; CB, CCC.
  Rated Voltage   IEC 60947-2; CB, CCC.
  Rated Current   1A~63A
  Breaking Capacity   10kA
  Isolation Function   /
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   B Curve (3.2In~4.8In), C Curve (6.4In~9.6In), D Curve (9.6In~14.4In)
  Mechanical Endurance   20000 times
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release
NDM1-125 Series MCB

Application

• C Curve: Usual inductive loads (Only C curve available for 125A)
• D Curve: Highly inductive loads
• Overload and short circuit protection

  Product Name   NDM1-125 Series MCB
  Standards and Certificates   UL1077, IEC 60947-2; UL1077, TÜV, CE, DIN, CCC.
  Rated Voltage   AC 230V/400V; DC60V
  Rated Current   63A, 80A, 100A, 125A
  Breaking Capacity   10kA
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   C Curve (6.4In~9.6In), D Curve (9.6In~14.4In)
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables up to 50 sq. mm
  Electric Accessories   Cables up to 50 sq. mm
NDB6-125 Series MCB

Application

• C Curve: Usual inductive loads (Only C curve available for 125A)
• D Curve: Highly inductive loads
• Overload and short circuit protection
• Control
• Isolation
• DC system protection

  Product Name   NDB6-125 Series MCB
  Standards and Certificates   UL1077, IEC 60947-2; TÜV, CE, DIN, CB, CCC
  Rated Voltage   AC 230V/400V; DC60V
  Rated Current   63A, 80A, 100A, 125A
  Breaking Capacity   15kA
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   C Curve (6.4In~9.6In), D Curve (9.6In~14.4In)
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables from 10 sq. mm to 50 sq. mm
  Electric Accessories   /
NDB2Z-63 Series DC MCB

Application

• B Curve: Non-inductive or Micro-inductive circuit
• C Curve: DC distribution system
• Short circuit and overload protection

  Product Name   NDB2Z-63 Series DC MCB
  Standards and Certificates   UL1077, IEC 60898-2; UL1077, TÜV, CE, CCC.
  Rated Voltage   1P – DC 125V/220V; 2P – DC 250V/440V
  Rated Current   1A~63A
  Breaking Capacity   10kA/6kA
  Isolation Function   Yes
  Number of Poles   1, 2 (3P & 4P are also available)
  Tripping Characteristics   B Curve (4In~7In), C Curve (7In~15In)
  Mechanical Endurance   20000 times
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release
NDG1 Series Disconnect Switch

Application

• Close, open or disconnect the circuit

  Product Name   NDG1 Series Disconnect Switch
  Standards and Certificates   IEC 60947-3; TÜV, CE, CCC.
  Rated Voltage   AC 230V/400V
  Rated Current   32A, 63A, 100A
  Breaking Capacity   /
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   /
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables from 4 sq. mm to 50 sq. mm
  Electric Accessories   Auxiliary Switch
NDM1L Series RC Unit

Application

• Clip onto the right side of NDM1 series MCB
• Protection against earth leakage faults

  Product Name   NDM1L Series RC Unit
  Standards and Certificates   IEC 61009-1 (NDM1L-32, NDM1L-50), IEC 60947-2 (NDM1L-100); CCC.
  Rated Voltage   AC230/400V (1PN, 2P); AC400V (3P, 3PN, 4P)
  Rated Current   /
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles  
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   Cables up to 10 sq. mm/ 25 sq. mm/ 50 sq. mm
  Electric Accessories   /
NDM1LG Series RC Unit

Application

• Clip onto the right side of NDM1-63 series MCB
• Protection against earth leakage and overvoltage

  Product Name   NDM1LG Series RC Unit
  Standards and Certificates   IEC 61009-1; CCC.
  Rated Voltage   AC 230V/400V (1PN, 2P)
  Rated Current   /
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   1P+N, 2P
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   Cables up to 10 sq. mm/ 25 sq. mm
  Electric Accessories   /
NDB1L Series RCBO

Application

• In TT/TN-S grounding system
• Phase and neutral protection against short circuit, overload and earth leakage

  Product Name   NDB1L Series RCBO
  Standards and Certificates   UL1053, IEC61009-1; UL1053, TÜV, CE and CCC.
  Rated Voltage   AC 230V/400V (1PN, 2P)
  Rated Current   6A, 10A, 16A, 20A, 25A, 32A
  Breaking Capacity   4.5kA
  Isolation Function   /
  Number of Poles   1P+N
  Tripping Characteristics   C Curve
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables up to 10 sq. mm
  Electric Accessories   /
NDB1LG Series RCBO

Application

• In TT/TN-S grounding system
• Phase and neutral protection against short circuit, overload and earth leakage.

  Product Name   NDB1LG Series RCBO
  Standards and Certificates   IEC 61009-1
  Rated Voltage   AC 230V
  Rated Current   6A, 10A, 16A, 20A, 25A, 32A
  Breaking Capacity   4.5kA
  Isolation Function   /
  Number of Poles   1P+N
  Tripping Characteristics   C Curve
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables up to 10 sq. mm
  Electric Accessories   /
NDB2LE Series RCBO

Application

• Protection against short circuit, overload and earth leakage.

  Product Name   NDB2LE Series RCBO
  Standards and Certificates   IEC 61009-1; TÜV, CE and CCC.
  Rated Voltage   AC 230V(1PN, 2P); AC 400V (3P, 3PN, 4P)
  Rated Current   1A~63A
  Breaking Capacity   10kA
  Isolation Function   /
  Number of Poles   1P+N, 2, 3, 3P+N, 4
  Tripping Characteristics   B, C & D Curve
  Mechanical Endurance  
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   /
NDB6LM Series RCBO

Application

• TT/TN-S grounding system
• Protection against overload, short circuit and earth leakage

  Product Name   NDB6LM Series RCBO
  Standards and Certificates   IEC 61009-1; TÜV, CE and CCC.
  Rated Voltage   AC 230V
  Rated Current   6A, 10A, 16A, 20A, 25A, 32A, 40A
  Breaking Capacity   10kA
  Isolation Function   /
  Number of Poles   1P+N
  Tripping Characteristics   B Curve, Curve
  Mechanical Endurance   /
  Wiring Capacity   Cables up to 25 sq. mm
  Electric Accessories   /
NDL6M Series RCCB

Application

• TT/TN-S grounding system
• Protection against residual current

  Product Name   NDL6M Series RCCB
  Standards and Certificates   IEC 61008-1; TÜV, CE and CCC.
  Rated Voltage   AC 230V (2P), AC 230V/400V (4P)
  Rated Current   16A, 25A, 40A, 63A, 80A, 100A
  Breaking Capacity   /
  Isolation Function   Yes
  Number of Poles   2, 4
  Tripping Characteristics   /
  Mechanical Endurance   20000 times
  Wiring Capacity   Cables up to 35 sq. mm
  Electric Accessories   /
NDA1 Series Modular Socket

Application

• Connect electric equipment

  Product Name   NDA1 Series Modular Socket
  Standards and Certificates   IEC 60884-1; CCC.
  Rated Voltage   AC 250V/440V
  Rated Current   10A, 16A, 25A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDA3 Series Modular Socket

Application

• Connect electric equipment

  Product Name   NDA3 Series Modular Socket
  Standards and Certificates   IEC 60884-1
  Rated Voltage   AC 250V
  Rated Current   10A, 16A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDU1 Series SPD

Application

• Used for surge protection of low-voltage AC power
• It can provide B level, C level or D level protection to ensure the safety of equipment.

  Product Name   NDU1 Series SPD
  Standards and Certificates   IEC 60643-1
  Rated Voltage   /
  Rated Current   /
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   1P+N, 2, 3, 3P+N, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDP2 Series Consumer Unit

Application

• Indoor application, AC50Hz/60Hz, 440V, normally under 35℃ (occasionally up to 60℃). Protection circuit breaker, switch, socket, and similar inside electrical components from outside impact and invasion.
• Can be widely used as enclosure of fixed electricity

  Product Name   NDP2 Series Consumer Unit
  Standards and Certificates   IEC 670; CCC.
  Rated Voltage   AC440V
  Rated Current   /
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDP1A Series Consumer Unit

Application

• Indoor application, AC50Hz/60Hz, 440V, normally under 35℃ (occasionally up to 60℃). Protection circuit breaker, switch, socket and similar inside electrical components from outside impact and invasion.
• Can be widely used as enclosure of fixed electricity

  Product Name   NDP1A Series Consumer Unit
  Standards and Certificates   IEC 670; CCC.
  Rated Voltage   AC 440V
  Rated Current   /
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
Molded Case Circuit Breakers

NDM2 Series MCCB

Application

NDM2 Series Molded Case Circuit Breaker will be suitable for in-frequency switching of circuits and starting of motors in 50Hz/60Hz circuits. The breaker can provide overload, short circuit and under-voltage protection to the circuit and power equipment co

  Product Name   NDM2 Series MCCB
  Standards and Certificates   IEC60947-1, IEC60947-2; TÜV, CE, CCC.
  Rated Voltage   AC 400V/690V
  Rated Current   10A~800A
  Breaking Capacity   25kA~100kA
  Isolation Function   Yes
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   2500 times ~ 10000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release, Under-voltage Release
NDM2Z Series DC MCCB

Application

NDM2Z series DC MCCB is are suitable for power distribution, circuit and equipment protection in DC circuit, with the function of overload and short circuit protection.

  Product Name   NDM2Z Series DC MCCB
  Standards and Certificates   IEC 60947-2
  Rated Voltage   DC 250V
  Rated Current   10~630A
  Breaking Capacity   15kA~50kA
  Isolation Function   /
  Number of Poles   2, 3
  Tripping Characteristics   /
  Mechanical Endurance   4000 times~ 10000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release, Under-voltage Release
NDM2Z Series DC MCCB

Application

NDM2Z series DC MCCB is are suitable for power distribution, circuit and equipment protection in DC circuit, with the function of overload and short circuit protection.

  Product Name   NDM2Z Series DC MCCB
  Standards and Certificates   IEC 60947-2
  Rated Voltage   DC 250V
  Rated Current   10~630A
  Breaking Capacity   15kA~50kA
  Isolation Function   /
  Number of Poles   2, 3
  Tripping Characteristics   /
  Mechanical Endurance   4000 times~ 10000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release, Under-voltage Release
NDM2L Series MCCB with Residual Current Protection

Application

The product can provide overload, short circuit and under-voltage protection to the circuit and power equipment concerned. In additional, it can also protect the circuit against fire disaster caused by long-term grounding error that can not be detected

  Product Name   NDM2L Series MCCB with Residual Current Protection
  Standards and Certificates   IEC60947-2
  Rated Voltage   AC 400V
  Rated Current   16~400A
  Breaking Capacity   50kA/65kA @ AC400V 50/60Hz
  Isolation Function   Yes
  Number of Poles   4
  Tripping Characteristics   /
  Mechanical Endurance   7000 times (for NDM2L-100); 6500 times (for NDM2L-225); 4000 times (for NDM2L-400).
  Wiring Capacity   /
  Electric Accessories   Auxiliary Switch, Alarm Switch, Shunt Release, Under-voltage Release
Air Circuit Breakers

NDW1 Series ACB

Application

NDW1 series Air Circuit Breaker is used in AC 50Hz distribution network for power distribution and circuit and equipments protection against overload, under-voltage, short-circuit and single-phase grounding fault. It can also be used as switch-disconnector

  Product Name   NDW1 Series ACB
  Standards and Certificates   IEC60947-2:2006; CE, CCC.
  Rated Voltage   AC 400V/690V
  Rated Current   400A~6300A
  Breaking Capacity   80kA~120kA
  Isolation Function   Yes
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   10000 times ~ 20000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Contact, Shunt Release, Closing Release, Under-voltage Release, Motor Operator for Electrical Charging
NDW1G Series Swtich Disconnector

Application

NDW1G series Switch Disconnector is used in low-voltage power distribution network for making and breaking the main circuit and isolating.

  Product Name   NDW1G Series Swtich Disconnector
  Standards and Certificates   IEC60947-3:2005; TÜV, CE, CCC, CB, DIN.
  Rated Voltage   AC 400V/690V; DC 1000V
  Rated Current   400A~6300A
  Breaking Capacity   /
  Isolation Function   Yes
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   10000 times~20000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Contact, Shunt Release, Closing Release, Under-voltage Release, Motor Operator for Electrical Charging
Automatic Transfer Switches

NDQ5 Series ATS

Application

NDQ5 series Automatic Transfer Switch is used in AC emergency power supply system with frequency of 50Hz and rated operational voltage of 400V. When one power supply fails, ATS can implement power changeover between normal power and standby power.

  Product Name   NDQ5 Series ATS
  Standards and Certificates   IEC 60947-6-1
  Rated Voltage   AC 400V
  Rated Current   16A~800A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDQ3 Series ATS

Application

NDQ3 Series automatic transfer switch is used in AC emergency power supply system with frequency of 50Hz and rated working voltage of 400V. When one power supply fails, A.T.S. switch to standby power supply automatically to ensure reliable power supply.

  Product Name   NDQ3 Series ATS
  Standards and Certificates   IEC 60947-6-1
  Rated Voltage   AC 400V
  Rated Current   32A~400A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   3000 times~5000 times
  Wiring Capacity   /
  Electric Accessories   /
NDQ2 Series ATS

Application

NDQ2 series Automatic Transfer Switch is suitable for transferring between two circuits of power supply (working power supply, standby power supply). NDQ2 series transfer switch take the miniature circuit breaker as the implementation component.

  Product Name   NDQ2 Series ATS
  Standards and Certificates   Part 6-1 of GB/T14048.11-2002
  Rated Voltage   AC 400V
  Rated Current   6A~63A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDQ1 Series ATS

Application

NDQ1 series Automatic Transfer Switch is suitable for transferring between two circuits of power supply (working power supply, standby power supply). NDQ1 series transfer switch take the molded case circuit breaker as the implementation component.

  Product Name   NDQ1 Series ATS
  Standards and Certificates   Part 6-1 of GB/T14048.11-2002
  Rated Voltage   AC 400V
  Rated Current   10A~630A
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   4000 times~8500 times
  Wiring Capacity   /
  Electric Accessories   /
AC Contactors & Relays

NDC1-115~780 Series AC Contactor

Application

NDC1- 115~780 series AC contactor is used to making or breaking the circuit and for frequent start AC motors from a distance. It can be easily equipped with auxiliary contacts group, pneumatic timer and such accessories.

  Product Name   NDC1-115~780 Series AC Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5; CCC.
  Rated Voltage   AC 400V, 690V, 1000V
  Rated Current   115A~780A (AC-3 @ AC 400V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   NF1 Series Auxiliary Contact Group, NS1 Series Pneumatic Timer
NDC2-06~16 Series AC Contactor

Application

NDC2 series AC Contactor is used to making or breaking the circuit in power system. It can also compose the motor starter together with thermal overload relay or electronic protection device to protect the circuit against overload.

  Product Name   NDC2-06~16 Series AC Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5; TüV, CE, CCC.
  Rated Voltage   AC 220V/230V, AC 380/400V, AC 660V/690V
  Rated Current   6A~16A (AC-3 @ AC 380V/400V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDC2-115~780 Series AC Contactor

Application

NDC2 series AC Contactor is used to making or breaking the circuit in power system. It can also compose the motor starter together with thermal overload relay or electronic protection device to protect the circuit against overload.

  Product Name   NDC2-115~780 Series AC Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5; TüV, CE, CCC.
  Rated Voltage   AC 220V/230V, AC 380/400V, AC 660V/690V
  Rated Current   115A~170A (AC-3 @ AC 380V/400V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDC3 Series Modular Contactor

Application

NDC3 series modular contactor is used to control micro-inductive loads for household and similar installations or control motor loads for household. It is widely used in home, hotels, buildings, shopping mall, gymnasium, etc to realize automatic control….

  Product Name   NDC3 Series Modular Contactor
  Standards and Certificates   IEC 61095; CCC.
  Rated Voltage   AC 250V (for 1P, 2P), AC 400V (for 3P, 4P)
  Rated Current   16A~63A (AC-7a)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDC1N-09~95 Series Reversing AC Contactor

Application

NDC1N-09~95 series reversing AC contactor is used to control dual powers and reversible operational motors or motors which can back braking. It can also be used as electro-magnetc starter when matched with thermal relay to protect the circuit.

  Product Name   NDC1N-09~95 Series Reversing AC Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5; CCC.
  Rated Voltage   AC 380/400V, AC 660V/690V
  Rated Current   9A~95A (AC-3, AC400V); 3.5A~44A (AC-4, AC400V).
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   NF1 Series Auxiliary Contact Group, NS1 Series Pneumatic Timer, NG1 Series Coil Suppressor Module
NDC1N-115~780 Series Reversing AC Contactor

Application

NDC1N-115~780 series reversing AC contactor is used to control dual powers and reversible operational motors or motors which can back braking. It can also match with thermal relay to protect the circuit against possible overload

  Product Name   NDC1N-115~780 Series Reversing AC Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5; CCC.
  Rated Voltage   AC 400V, 690V, 1000V
  Rated Current   115A~780A (AC-3 @ AC 400V); 52A~234A (AC-4 @ AC 400V).
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3, 4
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   NF1 Series Auxiliary Contact Group, NS1 Series Pneumatic Timer
NDK1 Series Capacitor-switching Contactor

Application

NDK1 series capacitor-switching contactor is used to making or breaking capacitor groups in low-voltage reactive power compensation equipments. It is equipped with surge refraining device so that it can effectively reduce the shocks on capacitor groups….

  Product Name   NDK1 Series Capacitor-switching Contactor
  Standards and Certificates   IEC 60947-4, IEC 60947-5
  Rated Voltage   AC 400V
  Rated Current   18A~87A (AC-6b @ AC 400V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   3
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDQ4 Series Star-delta Starter

Application

NDQ4 series star-delta starter is used to control 3-phase squirrel-cage motor which the power is 80kW and below. It is used to realize starting with the lower voltage by changing the stellated connection to delta. It can also be fitted with appropriated….

  Product Name   NDQ4 Series Star-delta Starter
  Standards and Certificates   IEC 60947-4
  Rated Voltage   AC 380V/400V, AC 660V/690V
  Rated Current   20A~164A (AC-3 @ AC 400V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
NDJ1(Z) Series Contactor-type Relay

Application

NDJ1(Z) series contactor-type relay is used in circuit of AC 50Hz/60Hz with rated voltage up to 380V or DC 220V to control various electrical-magnetic coils, amplify or carry signals.

  Product Name   NDJ1(Z) Series Contactor-type Relay
  Standards and Certificates   IEC 60947-5; TÜV, CE, CCC.
  Rated Voltage   AC 380, DC 220V
  Rated Current   0.95A (AC-15, 380V); 0.15A (DC-13, 220V)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   NF1/NF2 Series Auxiliary Contact Group, NS1 Series Pneumatic Timer, NG1 Series Coil Suppressor Module
NDR1 Series Electronic Thermal Overload Relay

Application

NDR1 series electronic thermal overload relay is used to protect 3-phase AC circuit and motor against overload, long time starting, phase default and imbalance current among phases. 3-phase thermal overload relay is used to protect motor and adjustable….

  Product Name   NDR1 Series Electronic Thermal Overload Relay
  Standards and Certificates   IEC 60947-1, IEC 60947-4; TÜV, CE, CCC.
  Rated Voltage   AC (50Hz/60Hz) 110V, 220V, 380V
  Rated Current   0.1A~40A (NDR1-38); 23A~95A (NDR1-95)
  Breaking Capacity   /
  Isolation Function   /
  Number of Poles   /
  Tripping Characteristics   /
  Mechanical Endurance   /
  Wiring Capacity   /
  Electric Accessories   /
Hydraulic-Magnetic Circuit Breakers

NDB5-63 Series CBE

Application

NDB5 series circuit breaker for equipment provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment,….

  Product Name   NDB5-63 Series CBE
  Standards and Certificates   UL1077, IEC 60934; UL1077 approval, TÜV, CE, CCC.
  Rated Voltage   DC 80V, AC 230V/400V (50Hz/60Hz)
  Rated Current   0.5A~63A; 20~150A (multi-pole in parallel)
  Breaking Capacity   10000A(DC80V); 3000A(AC230V/400V)
  Isolation Function   /
  Number of Poles   1, 1P+N(only for AC), 2, 3, 3P+N(only for AC)
  Tripping Characteristics   DC short/medium/long delay; AC short/medium/long delay
  Mechanical Endurance   10000 times
  Wiring Capacity   Cables up to 25 sq. mm
  Electric Accessories   Auxiliary Contact
NDB3-100 Series CBE

Application

NDB3 series circuit breaker for equipment provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment,….

  Product Name   NDB3-100 Series CBE
  Standards and Certificates   UL489A, UL1077, IEC 60934; UL489A listed, UL1077 approval, TÜV, CE, CCC.
  Rated Voltage   DC 80V, AC 230V/400V (50Hz/60Hz)
  Rated Current   1A~100A; F101A~400A; B175A~400A
  Breaking Capacity   7500A/5000A/4000A
  Isolation Function   Yes
  Number of Poles   1, 2, 3, 4
  Tripping Characteristics   DC short/medium/long delay; AC short/medium/long delay
  Mechanical Endurance   10000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Contact
NDB3-50 Series CBE

Application

NDB3 series circuit breaker for equipment provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment,….

  Product Name   NDB3-50 Series CBE
  Standards and Certificates   UL489A, UL1077, UL1500, IEC 60934; UL489A listed, UL1077 approval, UL1500 approval, TÜV, CE, CCC.
  Rated Voltage   DC 80V, AC 230V/400V (50Hz/60Hz)
  Rated Current   1A~50A
  Breaking Capacity   5000A
  Isolation Function   Yes
  Number of Poles   1, 2, 3(only for AC)
  Tripping Characteristics   DC short/medium/long delay; AC short/medium/long delay
  Mechanical Endurance   10000 times
  Wiring Capacity   /
  Electric Accessories   Auxiliary Contact
NDB3-30 Series CBE

Application

NDB3 series circuit breaker for equipment provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment,….

  Product Name   NDB3-30 Series CBE
  Standards and Certificates   UL489A, UL1077, IEC 60934; UL489A listed, UL1077 approval, TÜV, CE, CCC
  Rated Voltage   DC 80V, DC 65V, AC 250V (50Hz/60Hz)
  Rated Current   0.1A~30A
  Breaking Capacity   1500A/1000A/600A
  Isolation Function   Yes
  Number of Poles   1, 2
  Tripping Characteristics   DC short/medium delay; AC short/medium delay
  Mechanical Endurance   10000 times
  Wiring Capacity   /
  Electric Accessories   /
For most-up-to-date datasheet, please visit Shanghai Liangxin (Nader) official website at link: www.sh-liangxin.com  or contract us. Our Sales and Customer Service Team is more than happy in helping you to select the right Solutions and right Products!